Warranty: | 3 Year |
---|---|
Brand: | People Electrical |
Operation: | Automatic and Manual |
Samples: |
standard packing
|
---|
Customization: |
---|
Shipping Cost:
Estimated freight per unit. |
about shipping cost and estimated delivery time. |
---|
Payment Method: | |
---|---|
Initial Payment Full Payment |
Currency: | US$ |
---|
Return&refunds: | You can apply for a refund up to 30 days after receipt of the products. |
---|
Suppliers with verified business licenses
Model No.
RDQH5 | 125 | L | 4P | R | |||||
Model NO. | Frame Size | Breaker Type | Pole | Controller Type | |||||
Automatic Transfer Switch (ATS) |
Code 125 250 400 630 |
L: L type Circuit breaker M: M type Circuit breaker H: H type Circuit breaker |
3P: 3 Pole 4P: 4 Pole |
R: self-throw and self-reset S: self-throw and self not reset T: Mutual Backup |
Function Set | Set Range | Default |
1 Operation Mode | Auto, Manual | Auto |
2 Grid structure | Grid Net and Grid Net, Grid Net and Generator Power | Grid Net and Grid Net |
3 Work mode | Self throw-Self reset, Self throw-Self not reset, Mutual backup | Self throw-Self reset |
4 Buzzer alarm | ON, OFF | ON |
5 Monitor function | Overvoltage, Undervoltage, phase-loss detection. Set range of Overvoltage threshold 230V~280V, Undervoltage 140V~220VO | vervoltage set 270V,Undervotlage se 170V |
6 Normal turns Backup Time-delay | 1s~255s | 3s |
7 Backup turns Normal Time-delay | 1s~255s | 3s |
8 Both break delay | 0.5s~10s | 3s |
9 Phase sequence detect | ON, OFF | ON |
10 Fire linkage control | AC/DC12V~36V input to Both break | |
11 Voltage calibration | Can take 6 ways Voltage Calibration |
Frame Size Rated Current Inm(A) | 125 | 250 | 400 | 630 | ||||||||
Rated current Ie(A ) | 16,20,25,32,40 | 100,125,160,180, | 225,250,315, | 400,500,630 | ||||||||
50,63,80,100,125 | 200,225,250 | 350,400 | ||||||||||
Pole | 3P,4P | |||||||||||
F requency (Hz) | 50 | |||||||||||
Rated insulation voltage Ui (V ) | AC800 | |||||||||||
Rated impulse withstand voltage Uimp(kV) | 8 | |||||||||||
Rated operate voltage Ue (V ) | AC400 | |||||||||||
Breaker Type | L | M | H | L | M | H | L | M | H | L | M | H |
Rated short-circuit breaking capacity Icn (kA) | 35 | 50 | 85 | 35 | 50 | 85 | 50 | 65 | 100 | 50 | 65 | 100 |
Rated short-circuit connecting capacity Icm (kA) | 73.5 | 105 | 187 | 73.5 | 105 | 187 | 105 | 143 | 220 | 105 | 143 | 220 |
ATSE Type | CB Type | |||||||||||
Using Type | AC-33iB | |||||||||||
Ambient Temperature | -35°C~+70°C | |||||||||||
Electrical life (Times) | 1000 | 1000 | 1000 | 1000 | ||||||||
Mechanical life (Times) | 5000 | 5000 | 3000 | 2000 | ||||||||
Mini transfer time | ≤3s(Can be added the conversion time delay) |
Model NO. | L (mm) | W (mm) | H (mm) |
RDQH5- 125L/3P | 308 | 194 | 132 |
RDQH5- 125L/4P | 338 | 194 | 132 |
RDQH5- 125M(H)/3P | 308 | 194 | 149 |
RDQH5- 125M(H)/4P | 338 | 194 | 149 |
RDQH5-250L/3P | 347 | 209 | 151 |
RDQH5-250L/4P | 382 | 209 | 151 |
RDQH5-250M(H)/3P | 347 | 209 | 169 |
RDQH5-250M(H)/4P | 382 | 209 | 169 |
RDQH5-400L/3P | 490 | 309 | 215 |
RDQH5-400L/4P | 539.5 | 309 | 215 |
RDQH5-630L/3P | 568 | 328 | 216.5 |
RDQH5-630L/4P | 626 | 328 | 216.5 |
Suppliers with verified business licenses